Trouble shooting guide:

Before calling about a Backflow, refer to this simple procedure to identify the cause of discharge from the relief valve port.

After observing water discharge from relief valve port:

1. Close #2 shut off valve.  If discharge stops, the problem is a fouled second check.

2.  If discharge continues, open #4 testcock.  If discharge stops or is reduced, the problem is a fouled first check.

3.  If discharge continues, the problem is most likely in the relief valve.

SOLUTION:  Disassemble and clean affected components and remove debris from the backflow preventer. 